industrial-aiops-energy — 能源 edition (变电 / 电力)
The energy edition of Industrial-AIOps,
split out into its own repo: read-only OT connectors for substation / utility
telecontrol protocols, built on top of iaiops.core.
- IEC 60870-5-104 (
c104) — RTU / substation telemetry - DNP3 / IEEE 1815 (
pydnp3) — outstation monitoring - IEC 61850 MMS (
pyiec61850, linux-only wheel) — substation IED reads
It reuses the base package's shared governance (audit / budget / risk-tier / undo), cross-protocol brain (data-flow / alarm / OEE / downtime RCA on the normalized ISA-95/18.2 model), and MCP server infrastructure — this repo only adds the three energy connectors + their session builders + MCP tools. Read-first: no control-direction writes are exposed.
Why a separate repo
Energy targets a distinct buyer (utilities / substations), has heavier
platform-specific deps (pyiec61850 is a linux-only SWIG wheel; pydnp3 builds a
native ext), and its own compliance surface (电力监控系统安全防护). Splitting keeps
the base install light. See the base repo's docs/ENERGY-SPINOUT.md for the plan.
Install
pip install iaiops-energy[energy] # all three energy protocols
pip install iaiops-energy[iec104] # just IEC-104
iaiops-energy pulls in iaiops (the shared core) automatically.
Use (MCP)
iaiops-energy-mcp # brain + energy tools over stdio
Point a target at your substation gear in ~/.iaiops/config.yaml
(protocol: iec104|dnp3|iec61850, host, port, common_address / unit_id).
Validation status (honest)
The same honesty ladder as the base repo. Driver codec / API surface is verified
against the real libraries; the mock/monkeypatched unit tests run in CI without
hardware. See the base repo's docs/PREVIEW-VERIFICATION.md runbook for how a
protocol is promoted.
| Protocol | Status | Evidence |
|---|---|---|
| DNP3 / IEEE 1815 | verified (monitor path) | Real master↔outstation round-trip against a live opendnp3 outstation (pydnp3): is_online() reflects the real channel OnStateChange, and integrity_poll() (Class 0/1/2/3) returns the seeded binary/analog/counter database grouped by type. See tests/test_dnp3_live.py (@pytest.mark.integration, skips when pydnp3 is absent). No physical RTU. |
| IEC 60870-5-104 | preview (待核实) | Not yet live-verified (no gear / simulator in CI). |
| IEC 61850 (MMS) | verified (monitor path) | Real client↔server MMS round-trip against an in-process libiec61850 MMS server built with pyiec61850's server API: iec61850_device_directory lists the logical device (and browses its logical nodes / data objects), and iec61850_read returns a seeded measurand (TotW.mag.f, FC MX) over real ISO-on-TCP; a bad reference surfaces an MMS data-access error instead of a fabricated value. See tests/test_iec61850_live.py (@pytest.mark.integration, skips when pyiec61850 / its server API is absent). No physical IED. Read/monitor only — control / GOOSE / SV out of scope. |
DNP3 notes: read-only / monitor direction only (no control). pydnp3 0.1.0 ships no
wheel and needs a native opendnp3 build, so the live test runs in a Linux container;
its DNP3Manager.Shutdown() can block in a long-lived interpreter, so the connector
bounds teardown (_Pydnp3MasterAdapter.shutdown) and the test drives the round-trip
in a short-lived child process.
License